Product Description
Easy to install, ideal for energy mangement applications, as well as accurate metering using Elkor's Power Metering devices.
Unlike the standard 5A CTs, the MSCT Current Transformers do not produce high voltage surge when opened . They generate a low energy mA output and no special protection and/or shorting blocks are required. Maximum open secondary voltage is clamped at about 22 V peak.
Applications
- Ideal for use with Elkor Technologies Inc. Power Meters:
- WattsOn Power Transducer
- WattsOn-Mark II Advanced Energy Meter
- Current Transformers for the i-Spy AC Current Transducer.
- Current Transformers for the i-Snail-X AC Current Transducer.
- Secondary current transformers applied on 5 A leads of the existing CTs
Specifications
MSCT1 | MSCT2 | |
Primary Wire Window | 0.75' (19mm) |
1.25' (32mm) |
Maximum Continuous Current (Amps AC) |
200A | 600A |
Output @ Max Input (mA AC) | 26.67mA | 80mA |
Turns Ratio | 7500:1 | 7500:1 |
Insulation Class | 600V; 50-60Hz | |
Leads | AWG #20 (or #22), 8' (2.4m), CSA Type TEW, 600V, AWM Style 1015 | |
Overload | 1.5 x Max Input for 5 seconds | |
Max Open Circuit Voltage | Output Clamped at 22V peak |
MSCT1 | MSCT2 | |
A | 2.00' | 3.25' |
B | 2.10' | 3.35' |
C | 0.61' | 1.00' |
D | 0.75' | 1.25' |
E | 0.75' | 1.25' |